What is Type B waterproofing?
Type B waterproofing is 'Structurally Integral Protection.' It relies on the design and materials of the structure itself to be water-resistant. This is typically achieved using waterproof concrete (containing hydrophobic admixtures) and waterstops embedded in the construction joints (like hydrophilic strips or metal waterbars). While the concrete itself blocks water, the joints are the weak points, which is why MPS specializes in injection hose systems to seal these joints post-construction if needed.
Where the term comes from. BS 8102:2022, the UK code of practice for protection of below-ground structures against water from the ground, defines three types of protection. Type A is barrier protection: a membrane, tanking slurry or bonded sheet applied to the structure. Type B is structurally integral protection: the structure itself keeps the water out. Type C is drained protection: water is allowed through the wall and managed in a cavity drain membrane and sump. The 2022 revision also set out four grades of internal environment — Grade 1a and 1b (seepage or damp tolerable to varying degrees), Grade 2 (no water penetration but damp areas tolerable) and Grade 3 (dry, for habitable and sensitive use) — and the designer's job is to pick the type or combination of types that reliably delivers the grade the client needs.
What makes concrete Type B. The structure is designed as water-resisting concrete to BS EN 1992-3, the Eurocode for liquid-retaining and containment structures, which controls cracking rather than relying on a coating. BS EN 1992-3 sets tightness classes: Class 0 where some leakage is acceptable, Class 1 where leakage is limited to a small amount and through-cracks are held to a width of 0.05-0.2mm depending on the ratio of water head to wall thickness, Class 2 where no leakage is permitted and cracks must not pass through the section, and Class 3 where no leakage is permitted at all and special measures such as liners are needed. Most UK basements designed as Type B are Class 1, which is why the reinforcement in a water-resisting wall is heavier and more closely spaced than strength alone would require: it is there to keep cracks fine enough to self-heal. Admixtures — hydrophobic pore-blockers, crystalline products and the PUDLO and Sika systems commonly specified in the UK — reduce permeability and are usually part of a Type B specification, but BS 8102 does not require them; a correctly designed and placed plain concrete can be Type B, and an admixture cannot rescue a wall with a badly formed joint.
Why the joints decide it. Water-resisting concrete is only as good as its weakest discontinuity, and in a Type B structure those are the construction joints (including the kicker at the base of every wall), the junctions between slab and piles or pile caps, movement joints, tie-bolt holes, and every service penetration. Each has to be detailed: a cast-in PVC or hydrophilic waterbar at construction joints, a centre-bulb waterbar at movement joints, cast-in sleeves or puddle flanges at penetrations, and, increasingly, an injection hose laid along the joint with its ports brought out so the joint can be grouted later without breaking out if it weeps. That last detail is the reason Type B is maintainable in a way Type A is not.
What Type B can and cannot do on its own. BS 8102:2022 is clear that for Grade 3 (habitable) basements, and wherever the consequence of failure is high, a single type of protection is a risk, and it recommends combined protection: Type B concrete with a Type A membrane on the outside, or Type B with a Type C cavity drain system on the inside, so that a defect in one is caught by the other. NHBC Standards Chapter 5.4 takes the same line for basements in new homes it warrants, in most cases requiring two forms of protection. Type B alone is commonly used for car parks, plant rooms and storage (Grade 1 or 2), and for water-retaining structures such as tanks and attenuation structures designed to BS EN 1992-3.
What we do with Type B structures. MPS installs injection hose in construction joints during the pour on new build; and on existing structures that were designed as Type B and now leak, we seal the joints, cracks and penetrations from inside by resin injection, hydrophilic systems and fillet seals, without excavation — which is how a Type B structure is meant to be repaired. The Dumont on Albert Embankment, where we applied an internal render to a PUDLO water-resisting concrete attenuation tank, is a documented example of combined protection in practice.
Reviewed by Jerry Blears, Director (LinkedIn), MPS Concrete Solutions. Last reviewed October 2026.
BS 8102:2022 Compliance Checklist
Type B is one of the three forms of protection in BS 8102:2022. The checklist covers grades, combined protection, joint detailing and who is responsible for the design.
Read the full guideRelated Questions
How to Seal Pipes & Services Through Concrete
Our complete technical guide covers penetration sealing systems, fire rating requirements, hydrophobic and intumescent materials, and installation details for pipes, cables and ducts through concrete walls and floors.
Read the full guide